# ICS Advisory (ICSA-18-270-02)
## Fuji Electric Alpha5 Smart Loader (Update A)
Original release date: September 27, 2018 | Last revised: February 07, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-270-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-270-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-270-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 9.8**
* **ATTENTION:** Exploitable remotely/low skill level to exploit/public exploits are available
* **Vendor:** Fuji Electric
* **Equipment:** Alpha5 Smart Loader
* **Vulnerabilities:** Classic Buffer Overflow, Heap-based Buffer Overflow
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled
ICSA-18-270-02 Fuji Electric Alpha5 Smart Loader that was published September
27, 2018, on the NCCIC/ICS-CERT website. This advisory includes mitigations
for a classic buffer overflow and heap-based buffer overflow vulnerabilities
in the Fuji Electric Alpha5 Smart Loader product.
## 3\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow for arbitrary
remote code execution on the device.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
The following versions of Alpha5 Smart Loader, a servo drive, are affected:
* Alpha5 Smart Loader Versions 3.7 and prior
### 4.2 VULNERABILITY OVERVIEW
#### 4.2.1 [BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER
OVERFLOW') CWE-120](https://cwe.mitre.org/data/definitions/120.html)
A buffer overflow information disclosure vulnerability occurs when parsing
certain file types.
[CVE-2018-14788](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-14788)
has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N)).
#### 4.2.2 [HEAP-BASED BUFFER OVERFLOW
CWE-122](https://cwe.mitre.org/data/definitions/122.html)
The device does not perform a check on the length/size of a project file
before copying the entire contents of the file to a heap-based buffer.
[CVE-2018-14794](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-14794)
has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
### 4.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Commercial Facilities, Critical Manufacturing
* **COUNTRIES/AREAS DEPLOYED:** Europe and Asia
* **COMPANY HEADQUARTERS LOCATION:** Japan
### 4.4 RESEARCHER
Michael Flanders working with Trend Micro's Zero Day Initiative reported these
vulnerabilities to NCCIC.
## 5\. MITIGATIONS
**\--------- Begin Update A Part 1 of 1 ---------**
Fuji Electric has released a new version of the Alpha Loader software that can
be obtained from (login required):
[https://felib.fujielectric.co.jp/download/login.htm?site=global&lang=en](https://felib.fujielectric.co.jp/download/login.htm?site=global&lang=en)
**\--------- End Update A Part 1 of 1 ---------**
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.