# ICS Advisory (ICSA-18-317-08)
## Siemens SIMATIC Panels
Original release date: November 13, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-08)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-08)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-08)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** SIMATIC Panels
* **Vulnerabilities:** Path Traversal, Open Redirect
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow download of
arbitrary files from the device, or allow URL redirections to untrusted
websites.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
Siemens reports that these vulnerabilities affect the following SIMATIC
products:
* SIMATIC HMI Comfort Panels 4"-22" all versions prior to v15 Update 4,
* SIMATIC HMI Comfort Outdoor Panels 7" & 15" all versions prior to v15 Update 4,
* SIMATIC HMI KTP Mobile Panels all versions prior to v15 Update 4
* KTP400F,
* KTP700,
* KTP700F,
* KTP900 and
* KTP900F,
* SIMATIC WinCC Runtime Advanced all versions prior to v15 Update 4,
* SIMATIC WinCC Runtime Professional all versions prior to v15 Update 4,
* SIMATIC WinCC (TIA Portal) all versions prior to v15 Update 4, and
* SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) all versions.
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH
TRAVERSAL') CWE-22](https://cwe.mitre.org/data/definitions/22.html)**
A directory traversal vulnerability has been identified that could enable
download of arbitrary files from the device. The security vulnerability could
be exploited by an attacker with network access to the integrated web server.
[CVE-2018-13812](https://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-13812)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N)).
**3.2.2 [URL REDIRECTION TO UNTRUSTED SITE ('OPEN REDIRECT')
CWE-601](https://cwe.mitre.org/data/definitions/601.html)**
The webserver of affected HMI devices may allow URL redirections to untrusted
websites. An attacker must trick a valid user who is authenticated to the
device into clicking on a malicious link.
[CVE-2018-13813](https://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-13813)
has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Critical Manufacturing, Energy, Food and Agriculture, Healthcare and Public Health, Transportation.
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 3.4 RESEARCHER
Hosni Tounsi from Carthage Red Team // Carthage Cyber Services reported one of
these vulnerabilities to Siemens.
## 4\. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations
users can apply to reduce the risk:
* Update SIMATIC WinCC (TIA Portal) to v15 Update 4 or newer, then update panel to v15 Update 4 or newer. See:
<https://support.industry.siemens.com/cs/ww/en/view/109755826>
* Restrict network access to the integrated web server.
* Deactivate the web server if not required. The web server is disabled by default.
* Apply defense-in-depth.
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to Siemens' operational guidelines for industrial security
(download: <https://www.siemens.com/cert/operational-guidelines-industrial-
security>), and following the recommendations in the product manuals.
For more information on these vulnerabilities and associated software updates,
please see Siemens' security advisory SSA-233109 on their website:
<https://www.siemens.com/cert/advisories>[
](https://www.siemens.com/cert/advisories )
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.