# ICS Advisory (ICSA-18-317-03)
## Siemens SIMATIC Panels and SIMATIC WinCC (TIA Portal)
Original release date: November 13, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-03)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-03)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-03)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 4.3**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** SIMATIC Panels and SIMATIC WinCC (TIA Portal)
* **Vulnerability:** Code Injection
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker with
network access to the web server to perform a HTTP header injection attack.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
Siemens reports the vulnerability affects the following versions of SIMATIC
Panel software and SIMATIC WinCC (TIA Portal):
* SIMATIC HMI Comfort Panels 4" - 22": All versions prior to v14,
* SIMATIC HMI Comfort Outdoor Panels 7" and 15": All versions prior to v14,
* SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F: All versions prior to v14,
* SIMATIC WinCC Runtime Advanced: All versions prior to v14,
* SIMATIC WinCC Runtime Professional: All versions prior to v14,
* SIMATIC WinCC (TIA Portal): All versions prior to v14, and
* SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel): All versions.
### 3.2 VULNERABILITY OVERVIEW
### 3.2.1 [IMPROPER CONTROL OF GENERATION OF CODE ('CODE INJECTION')
CWE-94](https://cwe.mitre.org/data/definitions/94.html)
The integrated web server (Port 80/TCP and Port 443/TCP) of the affected
devices could allow an attacker to inject HTTP headers.
An attacker must trick a valid user who is authenticated to the device into
clicking on a malicious link to exploit the vulnerability.
[CVE-2018-13814](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-13814)
has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:L/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:L/A:N)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Energy, Food and Agriculture, and Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 3.4 RESEARCHER
Siemens reported this vulnerability to NCCIC.
## 4\. MITIGATIONS
Siemens has provided updates for the following products to fix the
vulnerability. The update can be located here:
<https://support.industry.siemens.com/cs/ww/en/view/109755826>
* SIMATIC HMI Comfort Panels 4" - 22": Update SIMATIC WinCC (TIA Portal) to v15 Update 4 or newer, and then update panel to v15 Update 4 or newer.
* SIMATIC HMI Comfort Outdoor Panels 7" & 15": Update SIMATIC WinCC (TIA Portal) to v15 Update 4 or newer, and then update panel to v15 Update 4 or newer.
* SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F: Update SIMATIC WinCC (TIA Portal) to v15 Update 4 or newer, and then update panel to v15 Update 4 or newer.
* SIMATIC WinCC Runtime Advanced: Update to v15 Update 4 or newer.
* SIMATIC WinCC Runtime Professional: Update to v15 Update 4 or newer.
* SIMATIC WinCC (TIA Portal): Update to v15 Update 4 or newer.
* SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel): Restrict network access to the integrated web server and deactivate the web server if not required. The web server is disabled by default.
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to Siemens' operational guidelines for industrial security
(download: <https://www.siemens.com/cert/operational-guidelines-industrial-
security>), and following the recommendations in the product manuals.
Additional information on industrial security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For more information on this vulnerability and associated software updates,
please see Siemens security advisory SSA-944083 on their website:
<https://www.siemens.com/cert/advisories>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.