# ICS Advisory (ICSA-19-134-06)
## Siemens SINAMICS PERFECT HARMONY GH180 Fieldbus Network
Original release date: May 14, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-134-06)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-134-06)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-134-06)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** SINAMICS PERFECT HARMONY GH180 Fieldbus Network
* **Vulnerability:** Improper Input Validation
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could cause a denial-of-service
condition.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
Siemens has determined this vulnerability applies to the following medium
voltage converters:
* SINAMICS PERFECT HARMONY GH180 with NXG I control, MLFBs: 6SR2. . . -, 6SR3. . . -, 6SR4. . . -: All versions with option G21, G22, G23, G26, G28, G31, G32, G38, G43 or G46
* SINAMICS PERFECT HARMONY GH180 with NXG II control, MLFBs: 6SR2. . . -, 6SR3. . . -, 6SR4. . . -: All versions with option G21, G22, G23, G26, G28, G31, G32, G38, G43 or G46
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [ IMPROPER INPUT VALIDATION
CWE-20](https://cwe.mitre.org/data/definitions/20.html)**
An improperly configured parameter read/write execution via fieldbus network
may cause the controller to restart. An attacker with access to the fieldbus
network could cause a denial-of-service condition by sending specially crafted
packets.
The vulnerability could be exploited by an attacker with network access to the
device. Successful exploitation requires no privileges and no user
interaction. An attacker could use the vulnerability to compromise the
availability of the affected system.
[CVE-2019-6574](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6574)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 3.4 RESEARCHER
Siemens reported this vulnerability to NCCIC.
## 4\. MITIGATIONS
Siemens recommends users upgrade to NXGpro control. Please contact Siemens
customer service to obtain and install the upgrade.
Siemens has identified the following specific workarounds and mitigations that
users can apply to reduce the risk:
* Disable the fieldbus parameter read/write functionality
* Apply cell protection concept and implement defense in depth
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to [Siemens' operational guidelines for industrial
security](https://assets.new.siemens.com/siemens/assets/public.1502968141.411e91564a2d259ecd4b6c79b51f89c044b3de81.operational-
guidelines-industrial-security-en.pdf) and to following the recommendations in
the product manuals.
Additional information on Industrial Security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For further inquiries about security vulnerabilities in Siemens products and
solutions, or for more information about this vulnerability and associated
software updates (outlined in SSA-865156), please contact the Siemens
ProductCERT through the website:
<https://www.siemens.com/cert/advisories>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.