# ICS Advisory (ICSA-20-154-01)
## ABB System 800xA
Original release date: June 02, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-154-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-154-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-154-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.3**
* **ATTENTION:** Low skill level to exploit
* **Vendor:** ABB
* **Equipment:** System 800xA
* **Vulnerabilities:** Incorrect Default Permissions
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to
escalate privileges, cause system functions to stop, and corrupt user
applications.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following products of System 800xA are affected:
* OPC Server for AC 800M: Versions 6.0 and prior
* Control Builder M Professional: Versions 6.1 and prior
* MMS Server for AC 800M: Versions 6.1 and prior
* Base Software for SoftControl: Versions 6.1 and prior
* ABB System 800xA Base: Versions 6.1 and prior
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [INCORRECT DEFAULT PERMISSIONS
CWE-276](https://cwe.mitre.org/data/definitions/276.html)
Weak access control lists for system folders could allow low privileged users
to modify system and application files.
[CVE-2020-8472](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8472)
has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been
calculated; the CVSS vector string is
([AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H)).
#### 3.2.2 [INCORRECT DEFAULT PERMISSIONS
CWE-276](https://cwe.mitre.org/data/definitions/276.html)
An attacker who successfully exploits the weak file permissions in one of the
ABB System 800xA functions could corrupt applications by escalating
privileges, executing arbitrary code, and affecting various engineering
functions.
[CVE-2020-8473](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8473)
has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been
calculated; the CVSS vector string is
([AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Critical Manufacturing, Dams, Energy, Food and Agriculture, Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Switzerland
### 3.4 RESEARCHER
William Knowles of Applied Risk reported these vulnerabilities to ABB.
## 4\. MITIGATIONS
ABB recommends changing any user account passwords suspected to be known by an
unauthorized person. Interactive logon (both local and remote) is recommended
to be disabled for the service account.
The vulnerabilities in the OPC Server for AC 800M was corrected in System
800xA 6.1
In the Control Builder M Professional, MMS Server for AC 800M and Base
Software for SoftControl and ABB System 800xA Base, the vulnerabilities will
be corrected in future releases of System 800xA. These vulnerabilities are
planned to be corrected in the next release on the 6.0.3 LTS track following
6.0.3.3
Please note these vulnerabilities can only be exploited by authenticated
users, so users are recommended to ensure only authorized persons have access
to user accounts in System 800xA.
For more information please refer to [ABB's Cybersecurity
Advisory](https://search.abb.com/library/Download.aspx?DocumentID=2PAA121106&LanguageCode=en&DocumentPartId=&Action=Launch).
CISA recommends users take defensive measures to minimize the risk of
exploitation of these vulnerabilities. Specifically, users should:
* Follow the principle of least privilege.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target these vulnerabilities. These
vulnerabilities are not exploitable remotely.