# ICS Advisory (ICSA-20-184-02)
## ABB System 800xA Information Manager
Original release date: July 02, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-184-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-184-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-184-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 8.8**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** ABB
* **Equipment:** System 800xA Information Manager
* **Vulnerability:** Cross-site Scripting
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to
inject and execute arbitrary code on the information manager server.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of System 800xA Information Manager are affected:
* Versions prior to 5.1 Rev E/5.1 FP4 Rev E TC6
* Versions prior to 6.0.3.3 RU1
* Versions prior to 6.1 RU1
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION
('CROSS-SITE SCRIPTING')
CWE-79](https://cwe.mitre.org/data/definitions/79.html)
The affected product is vulnerable to a remote code execution attack that may
allow an attacker to remotely execute arbitrary code. Successful exploitation
of this vulnerability requires luring a user (on a host with the vulnerable IM
component installed) to access a malicious website that instructs the user's
browser to load the vulnerable component before passing malicious input. This
could cause the Display Services functionality to stop or malfunction.
[CVE-2020-8477](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8477)
has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H))
### 3.3 BACKGROUND
**CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Critical Manufacturing, Dams,
Energy, Food and Agriculture, Water and Wastewater Systems
**COUNTRIES/AREAS DEPLOYED:** Worldwide
**COMPANY HEADQUARTERS LOCATION:** Switzerland
### 3.4 RESEARCHER
William Knowles of Applied Risk reported this vulnerability to ABB.
## 4\. MITIGATIONS
ABB's recommendations:
* This vulnerability was corrected in System 800xA of the following versions:
* 5.1 Rev E/5.1 FP4 E TC6, ABB recommends users on the 5.1 track to install this TC, which can be obtained from technical support upon request.
* 6.0.3.3 RU1, ABB recommends users on the 6.0.3 LTS track to update 6.0.3.3 and install RU1 for IM.
* 6.1 RU1, ABB recommends users on the 6.1 track to update to this version.
* The above-mentioned updates are recommended regardless of whether the previously described manual removal of the vulnerable component has been done or not. The IM rollups for 6.0.3.3 and 6.1 can be downloaded from My ABB/My Control System.
* Please note this vulnerability can be exploited by remote and unauthenticated users, so users are recommended to ensure only authorized persons have access to plant assets and network and that web browsing from system nodes to external networks is restricted, especially from an IM node.
* Check that the usage of the Access Enable key in AC 800M HI and the configured access level of SIL variables corresponds to the risk analysis.
Successful exploitation of this vulnerability requires luring a user to a
malicious website. Recommended baseline security practices and firewall
configurations can help protect a network and its attached devices from
attacks that originate from outside the network.
Recommended baseline security practices and firewall configurations can help
protect a network and its attached devices from attacks that originate from
outside the network. For example, common practices are for process control
systems to be physically protected from direct access by unauthorized
personnel, have no direct connections to the Internet, and are separated from
other networks by means of a firewall system that has a minimal number of
ports exposed, and others that must be evaluated case by case.
Process control and automation systems should not be used for general business
functions (e.g., Internet browsing, email, etc.) that are not critical
industrial processes. Portable computers and removable storage media should be
carefully scanned for viruses before they are connected to a control system.
Recommended practices include that process control systems are physically
protected, have no direct connections to the Internet, and are separated from
other networks by means of a firewall system with a minimal number of ports
exposed.
For more information please refer to ABB's [Cybersecurity
Advisory](https://search.abb.com/library/Download.aspx?DocumentID=2PAA121232&LanguageCode=en&DocumentPartId=&Action=Launch).
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target this vulnerability.