# ICS Advisory (ICSA-18-198-01)
## ABB Panel Builder 800
Original release date: July 17, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-198-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-198-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-198-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.0**
* **Vendor:** ABB
* **Equipment:** Panel Builder 800
* **Vulnerability:** Improper Input Validation
## 2\. RISK EVALUATION
An attacker could exploit the vulnerability by tricking a user to open a
specially crafted file, allowing the attacker to insert and run arbitrary
code. This vulnerability requires user interaction, and the exploit is only
triggered when a local user runs the affected product and loads the specially
crafted file.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of Panel Builder 800, an engineering tool for the
process panels included in the product suite Panel 800, are affected:
* Panel Builder 800, all versions.
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [IMPROPER INPUT VALIDATION
CWE-20](https://cwe.mitre.org/data/definitions/20.html)
An improper input validation vulnerability has been identified, which may
allow an attacker to insert and run arbitrary code on a computer where the
affected product is used.
[CVE-2018-10616](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-10616)
has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been
calculated; the CVSS vector string is
([AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Critical Manufacturing, Energy, Dams, Water and Wastewater, and Food and Agriculture
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Switzerland
### 3.4 RESEARCHER
Michael DePlante of Leahy Center and Michael Flanders of Trend Micro, both
working with Trend Micro's Zero Day Initiative, reported this vulnerability to
ABB. ABB reported it to NCCIC.
## 4\. MITIGATIONS
ABB is currently investigating this vulnerability and recommends users follow
these suggestions until a corrected version is available.
Recommended security practices and firewall configurations can help protect a
process control network from attacks that originate from outside the network.
Such practices include:
* Conduct or reinforce cybersecurity awareness training for users of Panel Builder 800:
* Describing general cybersecurity best practice recommendations for industrial control systems,
* Informing that it is possible to infect Panel Builder files with malware,
* Describing the importance of being careful with files that are received unexpectedly and/or from unexpected sources.
* Carefully inspecting any files transferred between computers, including scanning them with up-to-date antivirus software, so that only the legitimate files are being transferred.
* User account management, appropriate authentication and permission management using the principle of least privilege.
Please see the following cybersecurity advisory on the ABB website for more
information:
[http://search-
ext.abb.com/library/Download.aspx?DocumentID=3BSE092089&Action=Launch](http://search-
ext.abb.com/library/Download.aspx?DocumentID=3BSE092089&Action=Launch)
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This
vulnerability is not exploitable remotely. High skill level is needed to
exploit.