# ICS Advisory (ICSA-18-282-05)
## Siemens SIMATIC S7-1500, SIMATIC S7-1500 Software Controller and SIMATIC ET
200SP OpenController (Update A)
Original release date: October 09, 2018 | Last revised: February 12, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-282-05)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-282-05)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-282-05)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 5.3**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** SIMATIC S7-1500, SIMATIC S7-1500 Software Controller and SIMATIC ET 200SP Open Controller
* **Vulnerability:** Improper Input Validation
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled
ICSA-18-282-05 Siemens SIMATIC S7-1500, SIMATIC S7-1500 Software Controller
and SIMATIC ET 200SP OpenController that was published October 9, 2018, on the
NCCIC/ICS-CERT website.
## 3\. RISK EVALUATION
An attacker with network access to the PLC may be able to cause a denial-of-
service condition on the network stack.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
Siemens reports that this vulnerability affects the following products and
versions:
* Simatic S7-1500 (incl. F), all versions prior to v2.5 down to and including v2.0
* Simatic S7-1500 Software Controller all versions prior to v2.5 down to and including v2.0
**\--------- Begin Update A Part 1 of 2 ---------**
* Simatic ET 200SP Open Controller all versions prior to v2.5 down to and including v2.0
**\--------- End Update A Part 1 of 2 ---------**
### 4.2 VULNERABILITY OVERVIEW
### 4.2.1 [IMPROPER INPUT VALIDATION
CWE-20](https://cwe.mitre.org/data/definitions/20.html)
An attacker can cause a denial-of-service condition on the network stack by
sending a large number of specially crafted packets to the PLC. The PLC will
lose its ability to communicate over the network. This vulnerability could be
exploited by an attacker with network access to the affected systems.
Successful exploitation requires no privileges and no user interaction. An
attacker could use this vulnerability to compromise availability of the
network connectivity.
[CVE-2018-13805](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-13805)
has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been
calculated; the CVSS vector string is
[(AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L)](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).
### 4.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 4.4 RESEARCHER
Marcin Dudek, Jacek Gajewski, Kinga Staszkiewicz, Jakub Suchorab, and Joanna
Walkiewicz from National Centre for Nuclear Research Poland reported this
vulnerability to Siemens.
## 5\. MITIGATIONS
Siemens provides updates to address this vulnerability in these products and
recommends users update to the new version.
* SIMATIC S7-1500 Software Controller: Update to v2.5 or newer:
<https://support.industry.siemens.com/cs/us/en/view/109478528>
* SIMATIC S7-1500 incl. F: Update to v2.5 or newer:
<https://support.industry.siemens.com/cs/us/en/ps/13717/dl>
**\--------- Begin Update A Part 2 of 2-------- **
* SIMATIC ET-200SP Open Controller: Update to v2.1.6 or newer:
<https://support.industry.siemens.com/cs/us/en/view/109759122>
**\--------- End Update A Part 2 of 2-------- **
Siemens has identified the following specific workarounds and mitigations
users can apply to reduce the risk:
* Restrict network access to affected devices
* Apply cell-protection concept
* Apply defense-in-depth
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to Siemens' operational guidelines for industrial security
(<https://www.siemens.com/cert/operational-guidelines-industrial-security>),
and following the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For more information on this vulnerability and associated software updates,
please see Siemens security advisory SSA-347726 on their website:
<https://www.siemens.com/cert/advisories>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
暂无评论