# ICS Advisory (ICSA-18-317-05)
## Siemens SIMATIC S7 (Update A)
Original release date: November 13, 2018 | Last revised: March 12, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-05)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-05)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-05)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 5.3**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** SIMATIC S7
* **Vulnerability:** Resource Exhaustion
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled
ICSA-18-317-05 Siemens SIMATIC S7 that was published November 13, 2018, on the
NCCIC/ICS-CERT website.
## 3\. RISK EVALUATION
Successful exploitation of this vulnerability could result in a denial-of-
service condition that could result in a loss of availability of the affected
device.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
Siemens reports the following SIMATIC S7 products are affected:
**\--------- Begin Update A Part 1 of 2 -------- **
* SIMATIC S7-1200: All versions prior to v4.3, and
**\--------- End Update A Part 1 of 2 ---------**
* SIMATIC S7-1500: All versions prior to 2.6
### 4.2 VULNERABILITY OVERVIEW
**4.2.1 [UNCONTROLLED RESOURCE CONSUMPTION ('RESOURCE EXHAUSTION')
CWE-400](https://cwe.mitre.org/data/definitions/400.html)**
An attacker could exhaust the available connection pool of an affected device
by opening a sufficient number of connections to the device. Successful
exploitation requires an attacker to be able to send packets to Port 102/TCP
of the affected device.
[CVE-2018-13815](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-13815)
has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L)).
### 4.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems.
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 4.4 RESEARCHER
Younes Dragoni of Nozomi Networks reported this vulnerability to Siemens.
## 5\. MITIGATIONS
Siemens recommends users of SIMATIC S7-1500 update to Version 2.6, which can
be downloaded at the following location:
<https://support.industry.siemens.com/cs/de/en/view/109478459>
**\--------- Begin Update A Part 2 of 2 ---------**
* SIMATIC S7-1200 update to Version 4.3, which can be downloaded at the following location:
<https://support.industry.siemens.com/cs/us/en/view/109763919>
**\--------- End Update A Part 2 of 2 ---------**
Siemens has identified the following specific workarounds and mitigations
users can apply to reduce the risk:
* Protect network access to Port 102/TCP of affected devices
* Apply cell-protection concept
* Apply defense-in-depth
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to Siemens' operational guidelines for industrial security
(<https://www.siemens.com/cert/operational-guidelines-industrial-security>),
and following the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For more information on this vulnerability and associated software updates,
please see Siemens security advisory SSA-584286 on their website:
<https://www.siemens.com/cert/advisories>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
暂无评论