# ICS Advisory (ICSA-18-317-04)
## Siemens SCALANCE S
Original release date: November 13, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-04)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-04)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-317-04)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 4.7**
* **ATTENTION:** Exploitable remotely
* **Vendor:** Siemens
* **Equipment:** SCALANCE S
* **Vulnerability:** Cross-site Scripting
## 2\. RISK EVALUATION
If an attacker tricks a user into clicking a malicious link, the device could
allow arbitrary script injection (XSS).
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
Siemens reports the following SCALANCE S products are affected:
* SCALANCE S602: All versions prior to v4.0.1.1,
* SCALANCE S612: All versions prior to v4.0.1.1,
* SCALANCE S623: All versions prior to v4.0.1.1, and
* SCALANCE S627-2M: All versions prior to v4.0.1.1
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-
SITE SCRIPTING') CWE-79](https://cwe.mitre.org/data/definitions/79.html)**
The device could allow cross-site scripting (XSS) attacks if unsuspecting
users click a malicious link. User interaction is required for a successful
exploitation. The user must be logged into the web interface in order for the
exploitation to succeed.
[CVE-2018-16555](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-16555)
has been assigned to this vulnerability. A CVSS v3 base score of 4.7 has been
assigned; the CVSS vector string is
([AV:N/AC:H/PR:N/UI:R/S:C/C:L/I:L/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:C/C:L/I:L/A:N)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Communications, Critical Manufacturing, Dams, Defense Industrial Base, Energy, Food and Agriculture, Government Facilities, Transportation Systems, Water and Wastewater Systems.
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 3.4 RESEARCHER
Nelson Berg of Applied Risk reported this vulnerability to Siemens.
## 4\. MITIGATIONS
Siemens has recommended that users update to Version 4.0.1.1, which can be
found here:
[https://support.industry.siemens.com/cs/document/109477325/-delivery-release-
and-download-of-firmware-update-v4-0-1-1-for-scalance-s?dti=0&lc=en-
WW](https://support.industry.siemens.com/cs/document/109477325/-delivery-
release-and-download-of-firmware-update-v4-0-1-1-for-scalance-s?dti=0&lc=en-
WW)
Siemens has identified the following specific workarounds and mitigations that
users can apply to reduce the risk: Only access links from trusted sources in
the browser you use to access the SCALANCE S administration website.
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to Siemens' operational guidelines for industrial security
(<https://www.siemens.com/cert/operational-guidelines-industrial-security>),
and following the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For more information on this vulnerability and associated software updates,
please see Siemens security advisory SSA-242982 on their website:
<https://www.siemens.com/cert/advisories>
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
NCCIC also recommends that users take the following measures to protect
themselves from social engineering attacks:
* Do not click web links or open unsolicited attachments in email messages.
* Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
* Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploits specifically target this vulnerability. High skill
level is needed to exploit.