# ICS Advisory (ICSA-19-036-01)
## AVEVA InduSoft Web Studio and InTouch Edge HMI
Original release date: February 05, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-036-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-036-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-036-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 9.8**
* **ATTENTION** : Exploitable remotely/low skill level to exploit
* **Vendor** : AVEVA Software, LLC (AVEVA)
* **Equipment** : InduSoft Web Studio and InTouch Edge HMI (formerly InTouch Machine Edition)
* **Vulnerabilities** : Missing Authentication for Critical Function, Resource Injection
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow a remote attacker
to execute an arbitrary process using a specially crafted database connection
configuration file.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of AVEVA products are affected:
* InduSoft Web Studio prior to Version 8.1 SP3, and
* InTouch Edge HMI (formerly InTouch Machine Edition) prior to Version 2017 Update
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [MISSING AUTHENTICATION FOR CRITICAL FUNCTION
CWE-306](https://cwe.mitre.org/data/definitions/306.html)**
Code is executed under the program runtime privileges, which could lead to the
compromise of the machine.
[CVE-2019-6543](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6543)
has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
**3.2.2 [IMPROPER CONTROL OF RESOURCE IDENTIFIERS ('RESOURCE INJECTION')
CWE-99](https://cwe.mitre.org/data/definitions/99.html)**
An unauthenticated remote user could use a specially crafted database
connection configuration file to execute an arbitrary process on the server
machine.
[CVE-2019-6545](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6545)has
been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS** : Chemical, Commercial Facilities, Critical Manufacturing, Energy, Food and Agriculture, Transportation Systems, and Water and Wastewater
* **COUNTRIES/AREAS DEPLOYED** : Worldwide
* **COMPANY HEADQUARTERS LOCATION** : United Kingdom
### 3.4 RESEARCHER
AVEVA, working with Tenable Research, reported these vulnerabilities to NCCIC.
## 4\. MITIGATIONS
AVEVA recommends affected users upgrade to the latest version of affected
products. The following security updates address the vulnerabilities outlined
in this advisory. Software updates can be downloaded from the Global Customer
Support "Software Download" area or from the links below:
The latest version of InduSoft Web Studio can be found at:
<http://download.indusoft.com/81.3.0/IWS81.3.0.zip>
The latest version of InTouch Edge HMI can be found at (login required):
<https://softwaresupportsp.schneider-
electric.com/#/producthub/details?id=52354>
For information on how to reach AVEVA support for a specific product, please
refer to these links:
[AVEVA Software Global Customer Support
](https://softwaresupport.aveva.com/)and [InduSoft
Support](http://www.indusoft.com/support).
For the latest security information and security updates, please visit AVEVA's
[Security Central ](https://fs-
ext.invensys.com/adfs/ls/?wa=wsignin1.0&wtrealm=urn%3asharepoint%3asoftwaresupportsp.se&wctx=https%3a%2f%2fsoftwaresupportsp.schneider-
electric.com%2f_layouts%2f15%2fAuthenticate.aspx%3fSource%3d%252F#/securitycentral)(login
required) and [InduSoft Security Updates](http://www.indusoft.com/Products-
Downloads/Security-Hotfix-Updates).
AVEVA has published Security Bulletin LFSEC00000133 on their website at the
following location: <https://sw.aveva.com/hubfs/assets-2018/pdf/security-
bulletin/SecurityBulletin_LFSec133.pdf>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.