# ICS Advisory (ICSA-19-038-02)
## Siemens EN100 Ethernet Module
Original release date: February 07, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-038-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-038-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-038-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION** : Exploitable remotely/low skill level to exploit
* **Vendor** : Siemens
* **Equipment** : EN100 Ethernet module
* **Vulnerabilities** : Improper Input Validation
## 2\. RISK EVALUATION
The EN100 Ethernet module for the SWT 3000 management platform is affected by
security vulnerabilities that could allow an attacker to conduct a denial-of-
service attack over the network.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of EN100 Ethernet module, a communication module for
SWT 3000 management platform, are affected:
* Firmware variant IEC 61850 for EN100 Ethernet module version prior to 4.33
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [IMPROPER INPUT VALIDATION
CWE-20](https://cwe.mitre.org/data/definitions/20.html)**
Specially crafted packets to Port 102/TCP could cause a denial-of-service
condition in the affected products. A manual restart is required to recover
the EN100 module functionality of the affected devices.
[CVE-2018-11451
](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-11451)has been
assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
**3.2.2 [IMPROPER INPUT VALIDATION
CWE-](https://cwe.mitre.org/data/definitions/20.html)20**
Specially crafted packets to Port 102/TCP could cause a denial-of-service
condition in the EN100 module if oscillographs are running. A manual restart
is required to recover the EN100 module functionality.
[CVE-2018-11452
](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-11452)has been
assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned;
the CVSS vector string is
([AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS** : Energy
* **COUNTRIES/AREAS DEPLOYED** : Worldwide
* **COMPANY HEADQUARTERS LOCATION** : Germany
### 3.4 RESEARCHER
Victor Nikitin, Vladislav Suchkov, and Ilya Karpov from ScadaX reported these
vulnerabilities to Siemens.
## 4\. MITIGATIONS
Siemens has released update v4.33 for several affected products, is working on
updates for the remaining affected products, and recommends specific
countermeasures until fixes are available:
<https://support.industry.siemens.com/cs/us/en/view/109745821>
Siemens has identified the following specific workarounds and mitigations
users can apply to reduce the risk:
* Block access to Port 102/TCP.
For additional information see Siemens' security advisory SSA-325546 at the
following location:
<http://www.siemens.com/cert/en/cert-security-advisories.htm>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.