# ICS Advisory (ICSA-19-050-04)
## Rockwell Automation Allen-Bradley PowerMonitor 1000 (Update A)
Original release date: February 19, 2019 | Last revised: September 05, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-050-04)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-050-04)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-050-04)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 9.8**
* **ATTENTION:** Exploitable remotely/low skill level to exploit/public exploits are available
* **Vendor:** Rockwell Automation
* **Equipment:** Allen-Bradley PowerMonitor 1000
* **Vulnerabilities:** Cross-site Scripting and Authentication Bypass
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled
ICSA-19-050-04 Rockwell Automation Allen-Bradley PowerMonitor 1000 that was
published February 9, 2019, on the ICS webpage on us-cert.gov.
## 3\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow a remote attacker
to affect the confidentiality, integrity, and availability of the device.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
The following versions of PowerMonitor 1000, a monitoring platform, are
affected:
* PowerMonitor 1000, all versions.
### 4.2 VULNERABILITY OVERVIEW
**4.2.1 [IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-
SITE SCRIPTING') CWE-79](https://cwe.mitre.org/data/definitions/79.html)**
A remote attacker could inject arbitrary code into a targeted user's web
browser to gain access to the affected device.
[CVE-2018-19615](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-19615)
has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N)).
**4.2.2 [AUTHENTICATION BYPASS USING AN ALTERNATE PATH OR CHANNEL
CWE-288](https://cwe.mitre.org/data/definitions/288.html)**
A remote attacker may be able to use a proxy to enable functionality that is
typically available to those with administrative rights for the web
application, allowing the attacker to bypass authentication. Once bypassed,
the attacker could disrupt user settings and device configuration.
[CVE-2018-19616](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-19616)
has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
### 4.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Energy
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** United States
### 4.4 RESEARCHER
Luca Chiou of ACSI reported these vulnerabilities to NCCIC.
## 5\. MITIGATIONS
**\--------- Begin Update A Part 1 of 1 --------**
Rockwell Automation has released [FRN
4.019](https://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?Keyword=1408-&crumb=112),
which addresses the reported vulnerabilities.
Rockwell Automation reports CheckPoint Software Technologies has released IPS
rules to detect attempts to exploit CVE-2018-19615.
In the event a user can not apply the FRN 4.019 patch, Rockwell Automation
notes users can temporarily mitigate these vulnerabilities by disabling the
FTP port using the LCD configuration menu or in the configuration options.
Users can also disable access to the webpage using the LCD screen
configuration menu or in the configuration options.
For more information, [Rockwell Automation has released a security
notification](https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1084790)
(login required).
**\--------- End Update A Part 1 of 1 --------**
CISA recommends users take defensive measures to minimize the risk of
exploitation of these vulnerabilities. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/Recommended-Practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on [the ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.