# ICS Advisory (ICSA-19-078-01)
## AVEVA InduSoft Web Studio and InTouch Edge HMI
Original release date: March 19, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-078-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-078-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-078-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 6.5**
* **ATTENTION:** Low skill level to exploit
* **Vendor:** AVEVA
* **Equipment:** InduSoft Web Studio, InTouch Edge HMI
* **Vulnerability:** Uncontrolled Search Path Element
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could allow execution of
unauthorized code or commands.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of AVEVA InduSoft Web Studio and InTouch Edge HMI are
affected by a vulnerability in a third-party component, Gemalto Sentinel
UltraPro encryption keys.
* InduSoft Web Studio versions prior to v8.1 SP3
* InTouch Edge HMI versions prior to 2017 Update 3
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [UNCONTROLLED SEARCH PATH ELEMENT
CWE-427](https://cwe.mitre.org/data/definitions/427.html)**
The uncontrolled search path element vulnerability allows an attacker to load
and execute a malicious file from the ux32w.dll in third-party component
Sentinel UltraPro.
[CVE-2019-6534](https://nvd.nist.gov/vuln/detail/CVE-2019-6534) has been
assigned to this vulnerability. A CVSS v3 base score of 6.5 has been
calculated; the CVSS vector string is
([AV:L/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* C **RITICAL INFRASTRUCTURE SECTORS:** Commercial Facilities, Critical Manufacturing, Energy, Transportation Systems, and Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** United Kingdom
### 3.4 RESEARCHER
ADLab of Venustech reported this vulnerability to NCCIC.
## 4\. MITIGATIONS
AVEVA recommends that users upgrade to the latest versions located the
following links:
InduSoft Web Studio v8.1 SP3
<http://download.indusoft.com/81.3.0/IWS81.3.0.zip>
InTouch Edge HMI 2017 Update 3
<https://softwaresupportsp.schneider-
electric.com/#/producthub/details?id=52354> (login required)
Users who are unable to upgrade to the latest version of InduSoft Web Studio
or InTouch Edge HMI, can alternatively apply Security Update LFSec131:
<http://www.indusoft.com/download/patches/security/LFSec131.zip>
<https://softwaresupportsp.schneider-
electric.com/#/producthub/details?id=52410> (login required)
For addition information please see AVEVA Security Bulletin LFSEC00000131:
<https://sw.aveva.com/hubfs/assets-2018/pdf/security-
bulletin/SecurityBulletin_LFSec131.pdf>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This
vulnerability is not exploitable remotely.