# ICS Advisory (ICSA-19-087-01)
## Rockwell Automation PowerFlex 525 AC Drives
Original release date: March 28, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-087-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-087-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-087-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Rockwell Automation
* **Equipment:** PowerFlex 525 AC Drives
* **Vulnerability:** Resource Exhaustion
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could result in resource
exhaustion, denial of service, and/or memory corruption.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of PowerFlex 525, an AC drive, are affected:
* PowerFlex 525 AC Drives with embedded EtherNet/IP and Safety Versions 5.001 and earlier.
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [UNCONTROLLED RESOURCE CONSUMPTION ('RESOURCE EXHAUSTION')
CWE-400](https://cwe.mitre.org/data/definitions/400.html)**
A remote, unauthenticated threat actor can repeatedly send specific CIP
packets to an affected PowerFlex 525 drive, which may allow disruption of the
availability of the device.
[CVE-2018-19282](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-19282)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Critical Manufacturing
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** United States
### 3.4 RESEARCHER
Nicolas Merle of Applied Risk reported this vulnerability to Rockwell
Automation.
## 4\. MITIGATIONS
Rockwell Automation has released new firmware to address the vulnerability.
Download the latest version of the firmware from:
[https://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?Keyword=25B&crumb=112](https://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?Keyword=25B&crumb=112)
Rockwell Automation recommends the following general security guidelines:
* Utilize proper network infrastructure controls, such as firewalls, to help ensure CIP messages from unauthorized sources are blocked.
* Block all traffic to EtherNet/IP or other CIP protocol-based devices from outside the manufacturing zone by blocking or restricting access to TCP and UDP Port 2222 and Port 44818, using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID [898270](https://rockwellautomation.custhelp.com/app/answers/detail/a_id/898270/page/1) (login required).
* If applicable, consult the product documentation for specific features, such as a hardware key-switch setting, which may be used to block unauthorized changes, etc.
* Use trusted software, software patches, antivirus/antimalware programs, and interact only with trusted websites and attachments.
* Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet or the business network.
* When remote access is required, use secure methods such as virtual private networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
Rockwell Automation has released a security advisory regarding this
vulnerability, which can be found on its website at the following location
(login required):
<https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1082684>
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
暂无评论