# ICS Advisory (ICSA-19-134-04)
## Siemens LOGO!8 BM
Original release date: May 14, 2019 | Last revised: May 15, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-134-04)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-134-04)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-134-04)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 9.4**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** LOGO!8 BM
* **Vulnerabilities:** Missing Authentication for Critical Function, Improper Handling of Extra Values, Plaintext Storage of a Password
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow device
reconfiguration, access to project files, decryption of files, and access to
passwords.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of Siemens LOGO!8 BM, a programmable logic controller,
are affected:
* Siemens LOGO!8 BM: all versions
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [MISSING AUTHENTICATION FOR CRITICAL FUNCTION
CWE-306](https://cwe.mitre.org/data/definitions/306.html)**
Attackers with access to Port 10005/TCP could perform device reconfigurations
and obtain project files from the devices.
[CVE-2019-10919](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-10919)
has been assigned to this vulnerability. A CVSS v3 base score of 9.4 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L)).
**3.2.2 [IMPROPER HANDLING OF EXTRA VALUES
CWE-231](https://cwe.mitre.org/data/definitions/231.html)**
Project data stored on the device, which is accessible via Port 10005/TCP, can
be decrypted due to a hardcoded encryption key.
[CVE-2019-10920](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-10920)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N)).
**3.2.3 [PLAINTEXT STORAGE OF A PASSWORD
CWE-256](https://cwe.mitre.org/data/definitions/256.html)**
Unencrypted storage of passwords in the project could allow an attacker with
access to Port 10005/TCP to obtain passwords of the device.
[CVE-2019-10921](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-10921)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Commercial Facilities, Transportation Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 3.4 RESEARCHER
Manuel Stotz and Matthias Deeg from SySS GmbH reported these vulnerabilities
to Siemens.
## 4\. MITIGATIONS
The LOGO!8 BM manual recommends protecting access to Port 10005/TCP.
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to [Siemens' operational guidelines for industrial
security](https://assets.new.siemens.com/siemens/assets/public.1502968141.411e91564a2d259ecd4b6c79b51f89c044b3de81.operational-
guidelines-industrial-security-en.pdf) and following the recommendations in
the product manuals.
Additional information on industrial security for Siemens devices can be found
at:
<https://www.siemens.com/industrialsecurity>
For more information on these vulnerabilities and more detailed mitigation
instructions, please see Siemens Security Advisory SSA-542701 at the following
location:
<http://www.siemens.com/cert/advisories>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of these vulnerabilities. Specifically, users should:
Minimize network exposure for all control system devices and/or systems, and
ensure that they are [not accessible from the Internet](/ics/alerts/ICS-
ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
暂无评论