# ICS Advisory (ICSA-19-162-03)
## Siemens LOGO!8 Devices
Original release date: June 11, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-162-03)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-162-03)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-162-03)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** LOGO!8 devices
* **Vulnerabilities:** Improper Restriction of Operations within the Bounds of a Memory Buffer, Session Fixation
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to
read the communication between the affected device and a user, and compromise
the availability of the targeted system.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of LOGO!8 devices, that are used for basic small-scale
automation tasks, are affected:
* SIEMENS LOGO!8: 6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware v1.80.xx and v1.81.xx
* SIEMENS LOGO!8: 6ED1052-xyy08-0BA0 FS:01 / Firmware version prior to v1.82.02
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY
BUFFER CWE-119](https://cwe.mitre.org/data/definitions/119.html)**
An attacker with network access to Port 10005/TCP of the LOGO!8 device could
cause a denial-of-service condition by sending specially crafted packets. This
security vulnerability could be exploited by an unauthenticated attacker with
network access to the affected service. No user interaction is required, and
successful exploitation could compromise the availability of the targeted
system.
[CVE-2019-6571](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6571)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
**3.2.2 [SESSION FIXATION
CWE-384](https://cwe.mitre.org/data/definitions/384.html)**
The integrated webserver does not invalidate the Session ID upon user logout.
An attacker who successfully extracted a valid Session ID is able to use it
even after the user logs out. This security vulnerability could be exploited
by an attacker in a privileged network position who is able to read the
communication between the affected device and the user, or by an attacker who
is able to obtain valid Session IDs through other means. To facilitate this
exploit, the user must first invoke a session to the affected device.
[CVE-2019-6584](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6584)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
assigned; the CVSS vector string is
([AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Commercial Facilities, Transportation Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 3.4 RESEARCHER
Thomas Meesters from cirosec GmbH and Ruhr University of Bochum, and Christian
Siemers and Irakli Edjibia from Hochschule Augsburg reported these
vulnerabilities to Siemens.
## 4\. MITIGATIONS
For Siemens LOGO!8: 6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version
v1.80.xx and v1.81.xx: Siemens recommends upgrading to a new version.
Siemens has updates at
<https://support.industry.siemens.com/cs/ww/en/view/109767410> for the
following product:
* Siemens LOGO!8: 6ED1052-xyy08-0BA0 FS:01 / Firmware version prior to v1.82.02: Update to vV1.82.02 or higher.
Siemens has identified the following specific workarounds and mitigations
users can apply to reduce the risk:
* Protect network access to the device.
* As a general security measure Siemens strongly recommends protecting network access to the devices with appropriate mechanisms.
* In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for Industrial Security (<https://cert-portal.siemens.com/operational-guidelines-industrial-security.pdf>), and following the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For more information on these vulnerabilities and more detailed mitigation
instructions, please see Siemens security advisory SSA-774850 at the following
location: <http://www.siemens.com/cert/advisories>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of these vulnerabilities. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
NCCIC also recommends that users take the following measures to protect
themselves from social engineering attacks:
* Do not click web links or open unsolicited attachments in email messages.
* Refer to [Recognizing and Avoiding Email Scams](/reading_room/emailscams_0905.pdf) for more information on avoiding email scams.
* Refer to [Avoiding Social Engineering and Phishing Attacks](/cas/tips/ST04-014.html) for more information on social engineering attacks.
No known public exploits specifically target these vulnerabilities. High skill
level is needed to exploit.
暂无评论