# ICS Advisory (ICSA-19-190-02)
## Rockwell Automation PanelView 5510
Original release date: July 09, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-190-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-190-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-190-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION:** Exploitable remotely
* **Vendor:** Rockwell Automation
* **Equipment:** PanelView 5510
* **Vulnerability:** Improper Access Control
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could allow a remote
unauthenticated user to gain root privileges on the device.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of PanelView 5510, an HMI, are affected:
* All versions manufactured before March 13, 2019, that have never been updated to v4.003, v5.002, or later.
### 3.2 VULNERABILITY OVERVIEW
### 3.2.1 [IMPROPER ACCESS CONTROL
CWE-284](https://cwe.mitre.org/data/definitions/284.html)
A remote, unauthenticated threat actor with access to an affected PanelView
5510 Graphic Display, upon successful exploit, may boot-up the terminal and
gain root-level access to the device's file system.
[CVE-2019-10970](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-10970)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Critical Manufacturing, Food and Agriculture, Transportation, Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** United States
### 3.4 RESEARCHER
Rockwell Automation reported this vulnerability to NCCIC.
## 4\. MITIGATIONS
Rockwell Automation reports users using PanelView 5510 with manufacturing
dates prior to March 13, 2019, are encouraged to update to an available
revision that addresses the associated risk.
For PanelView 5510 using v4, apply v4.003 or later and for PanelView 5510
using v5, apply v5.002 or later. Updates are available at:
[https://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?Keyword=5510&crumb=112](https://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?Keyword=5510&crumb=112)
(login required)
Rockwell Automation also recommends applying the following specific
mitigations:
* Block all traffic to EtherNet/IP or other CIP protocol-based devices from outside the manufacturing zone by blocking or restricting access to Ports 2222 and 44818/TCP and UDP using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances.
* Use trusted software, software patches, antivirus/anti-malware programs, and interact only with trusted websites and attachments.
For more information see Rockwell Automation security advisory 1088080 found
at:
<http://www.rockwellautomation.com/knowledgebase> (login required)
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://ics-cert.us-cert.gov/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](https://ics-cert.us-cert.gov/content/recommended-practices) on the
ICS-CERT web page. Several recommended practices are available for reading and
download, including [Improving Industrial Control Systems Cybersecurity with
Defense-in-Depth Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](https://ics-cert.us-cert.gov/) in the
Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://ics-cert.us-cert.gov/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.