# ICS Advisory (ICSA-19-190-01)
## Emerson DeltaV Distributed Control System
Original release date: July 09, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-190-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-190-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-190-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 6.1**
* **ATTENTION:** Low skill level to exploit
* **Vendor:** Emerson
* **Equipment:** DeltaV Distributed Control System (DCS)
* **Vulnerability:** Use of Hard-coded Credentials
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to gain
administrative access to DeltaV Smart Switches.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of DeltaV DCS, a software management platform, include
the vulnerable Smart Switch Command Center:
* 11.3.x
* 12.3.x
### 3.2 VULNERABILITY OVERVIEW
### 3.2.1 [USE OF HARD-CODED CREDENTIALS
CWE-798](https://cwe.mitre.org/data/definitions/798.html)
The Smart Switch Command Center does not change the DeltaV Smart Switch
management account password upon commissioning as expected, leaving the
default password in effect indefinitely.
[CVE-2018-11691](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-11691)
has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been
calculated; the CVSS vector string is
([AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Critical Manufacturing, Energy
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** United States
### 3.4 RESEARCHER
Benjamin Crosasso of Sanofi reported this vulnerability to Emerson.
## 4\. MITIGATIONS
Emerson recommends users patch affected products. Details are available within
article DSN19003 (KBA# NK-1900-0808). Software patches and DSN19003 are
available to users with access to the Emerson Guardian Support Portal at the
following link:
<https://guardian.emersonprocess.com/> (Login Required)
To limit exposure to these and other vulnerabilities, Emerson recommends that
DeltaV systems and related components be deployed and configured as described
in the DeltaV security manual, which can be found in Emerson's Guardian
Support Portal.
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://ics-cert.us-cert.gov/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](https://ics-cert.us-cert.gov/content/recommended-practices) on the
ICS-CERT web page. Several recommended practices are available for reading and
download, including [Improving Industrial Control Systems Cybersecurity with
Defense-in-Depth Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](https://ics-cert.us-cert.gov/) in the
Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://ics-cert.us-cert.gov/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This
vulnerability is not exploitable remotely.
暂无评论