# ICS Advisory (ICSA-19-213-03)
## 3S-Smart Software Solutions GmbH CODESYS V3
Original release date: August 01, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-213-03)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-213-03)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-213-03)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 9.0**
* **ATTENTION** : Exploitable remotely/low skill level to exploit
* **Vendor** : 3S-Smart Software Solutions GmbH
* **Equipment** : CODESYS V3
* **Vulnerabilities** : Unverified Ownership, Uncontrolled Memory Allocation
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow a remote attacker
to close existing communication channels or to take over an already
established user session to send crafted packets to a PLC.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
All variants of the following CODESYS V3 products in all versions prior to
v3.5.14.20 that contain the CmpGateway component are affected, regardless of
the CPU type or operating system:
* CODESYS Control for BeagleBone
* CODESYS Control for emPC-A/iMX6
* CODESYS Control for IOT2000
* CODESYS Control for Linux
* CODESYS Control for PFC100
* CODESYS Control for PFC200
* CODESYS Control for Raspberry Pi
* CODESYS Control V3 Runtime System Toolkit
* CODESYS Gateway V3
* CODESYS V3 Development System
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [UNVERIFIED OWNERSHIP
CWE-283](https://cwe.mitre.org/data/definitions/283.html)**
The CODESYS Gateway does not correctly verify the ownership of a communication
channel.
[CVE-2019-9010](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-9010)
has been assigned to this vulnerability. A CVSS v3 base score of 9.0 has been
assigned; the CVSS vector string is
([AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H)).
**3.2.2 [UNCONTROLLED MEMORY ALLOCATION
CWE-789](https://cwe.mitre.org/data/definitions/789.html)**
A crafted communication request may cause uncontrolled memory allocations in
the affected CODESYS products and may result in a denial-of-service condition.
[CVE-2019-9012
](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-9012) has been
assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS** : Critical Manufacturing
* **COUNTRIES/AREAS DEPLOYED** : Worldwide
* **COMPANY HEADQUARTERS LOCATION** : Germany
### 3.4 RESEARCHER
3S-Smart Software Solutions GmbH reported these vulnerabilities to CISA.
## 4\. MITIGATIONS
3S-Smart Software Solutions GmbH has released v3.5.14.20 and v3.5.15.0. Each
of these releases solve the noted vulnerabilities issues.
Please visit the CODESYS update area for more information on how to obtain the
software update: <https://www.codesys.com/download/>
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.