# ICS Advisory (ICSA-19-346-03)
## Omron PLC CJ, CS and NJ Series
Original release date: December 12, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-346-03)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-346-03)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-346-03)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 6.5**
* **ATTENTION** : Exploitable remotely/low skill level to exploit
* **Vendor** : Omron
* **Equipment** : PLC CJ, CS and NJ Series
* **Vulnerability** : Improper Restriction of Excessive Authentication Attempts
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to brute
force login credentials, obtain unauthorized access of the system, and may
allow an attacker unauthorized access to the FTP interface.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of Omron Programmable Logic Controllers are affected:
* Omron PLC CS series, all versions
* Omron PLC CJ series, all versions
* Omron PLC NJ series, all versions
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [IMPROPER RESTRICTION OF EXCESSIVE AUTHENTICATION ATTEMPTS
CWE-307](https://cwe.mitre.org/data/definitions/307.html)**
The software does not implement sufficient measures to prevent multiple failed
authentication attempts within in a short time frame, making it more
susceptible to brute force attacks.
[CVE-2019-18261](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-18261)
has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS** : Critical Manufacturing
* **COUNTRIES/AREAS DEPLOYED** : Worldwide
* **COMPANY HEADQUARTERS LOCATION** : Japan
### 3.4 RESEARCHER
n0b0dy reported this vulnerability to CISA.
## 4\. MITIGATIONS
Omron recommends the following mitigation measures:
* Filter FTP port: Protect access to Omron's PLC with a firewall and block unnecessary remote access to FTP port (default: 21).
* Filter IP addresses: Protect access to Omron's PLC with a firewall and filtering devices connected to the PLC by IP address.
* Ensure the use of strong passwords.
For more information provided by Omron on these vulnerabilities refer to this
[Omron report](http://www.omron-cxone.com/security/2019-12-06_PLC_EN.pdf).
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target this vulnerability.
暂无评论