# ICS Advisory (ICSA-18-165-01)
## Siemens SCALANCE X Switches, RUGGEDCOM WiMAX, RFID 181-EIP, and SIMATIC RF182C (Update C)
Original release date: January 14, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-165-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-165-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-165-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION:** Exploitable from the same local network segment (OSI Layer 2)
* **Vendor:** Siemens
* **Equipment:** SCALANCE X switches, RUGGEDCOM Win, RFID 181-EIP, and SIMATIC RF182C
* **Vulnerability:** Heap-based Buffer Overflow
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the advisory update titled
ICSA-18-165-01 Siemens SCALANCE X Switches, RUGGEDCOM WiMAX, RFID 181-EIP, and
SIMATIC RF182C (Update B) that was published June 11, 2019, on the ICS webpage
on us-cert.gov.
## 3\. RISK EVALUATION
By sending a specially crafted DHCP response to a client's DHCP request, an
unprivileged remote attacker could execute arbitrary code.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
Siemens reports the vulnerability affects the following products:
* RFID 181-EIP: All versions
* RUGGEDCOM Win: v4.4, v4.5, v5.0, and v5.1
**\--------- Begin Update C Part 1 of 3 ---------**
* SCALANCE X-200 switch family (incl. SIPLUS NET variants): All versions prior to v5.2.3
* SCALANCE X-200 IRT switch family (incl. SIPLUS NET variants): All versions prior to v5.4.1
* SCALANCE X-200RNA: All versions prior to v3.2.6
* SCALANCE X-300 switch family (incl. SIPLUS NET variants): All versions prior to v4.1.3
* SCALANCE X408: All versions prior to v4.1.3
**\--------- End Update C Part 1 of 3 ---------**
* SCALANCE X414: All versions
* SIMATIC RF182C: All versions
### 4.2 VULNERABILITY OVERVIEW
#### 4.2.1 [HEAP-BASED BUFFER OVERFLOW
CWE-122](https://cwe.mitre.org/data/definitions/122.html)
Unprivileged remote attackers located in the same local network segment (OSI
Layer 2) could gain remote code execution on the affected products by sending
a specially crafted DHCP response to a client's DHCP request.
[CVE-2018-4833](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-4833)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H)).
### 4.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, and Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 4.4 RESEARCHER
Dr. Ang Cui and Joseph Pantoga from Red Balloon Security reported this
vulnerability to Siemens Product CERT.
**\--------- Begin Update C Part 2 of 3 ---------**
Artem Zinenko from Kaspersky identified that SIPLUS should also be mentioned.
**\--------- End Update C Part 2 of 3 ---------**
## 5\. MITIGATIONS
Siemens has provided updates for the following products to fix the
vulnerability:
* RUGGEDCOM Win: [Update to v5.2](https://support.industry.siemens.com/cs/ww/en/view/109762466)
* SCALANCE X-200: [Update to v5.2.3](https://support.industry.siemens.com/cs/cn/en/view/109758142)
* SCALANCE X-200 IRT: [Update to v5.4.1](https://support.industry.siemens.com/cs/de/en/view/109758144)
* SCALANCE X-200RNA: [Update to v3.2.6](https://support.industry.siemens.com/cs/ww/en/view/109767359)
**\--------- Begin Update C Part 2 of 3 ---------**
* SCALANCE X-300 & SCALANCE X408: [Update to v4.1.3](https://support.industry.siemens.com/cs/document/109773547)
**\--------- End Update C Part 3 of 3 ---------**
Siemens has identified the following specific workarounds and mitigations that
customers can apply to reduce the risk:
* Use static IP addresses instead of DHCP
* Apply [cell protection concept](https://www.siemens.com/cert/operational-guidelines-industrial-security).
* Apply [Defense-in-Depth](https://www.siemens.com/cert/operational-guidelines-industrial-security).
As a general security measure, Siemens strongly recommends users protect
network access to devices with appropriate mechanisms. In order to operate the
devices in a protected IT environment, Siemens recommends users configure the
environment according to [Siemens' operational guidelines for Industrial
Security](https://cert-portal.siemens.com/operational-guidelines-industrial-
security.pdf), and follow the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For more information on this vulnerability and associated software updates,
please see [Siemens security advisory
SSA-181018](https://www.siemens.com/cert/advisories)
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target this vulnerability. High skill
level is needed to exploit.