# ICS Advisory (ICSA-20-051-01)
## B&R Automation Studio and Automation Runtime
Original release date: February 20, 2020 | Last revised: February 27, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-051-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-051-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-051-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 9.4**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** B&R Industrial Automation GmbH
* **Equipment:** Automation Studio and Automation Runtime
* **Vulnerability:** Improper Authorization
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability may allow a remote attacker to
modify the configuration of affected devices.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of B&R products are affected:
* Automation Studio Versions 2.7, 3.0.71, 3.0.80, 3.0.81, 3.0.90, 4.0.x to 4.6.4, and 4.7.2
* Automation Runtime Versions 2.96, 3.00, 3.01, 3.06, 3.07, 3.08 to 3.10, 4.00 to 4.03, 4.04 to 4.03, 4.04 to 4.63, 4.72 and above.
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [IMPROPER AUTHORIZATION
CWE-285](https://cwe.mitre.org/data/definitions/285.html)
The affected products are vulnerable to a weakness in SNMP service, which
allows unauthenticated users to modify the configuration via the service.
[CVE-2019-19108](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-19108)
has been assigned to this vulnerability. A CVSS v3 base score of 9.4 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Critical Manufacturing, Energy
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Austria
### 3.4 RESEARCHER
Yehuda Anikster and Amir Preminger of Claroty reported this vulnerability to
CISA.
## 4\. MITIGATIONS
B&R reports product-technical reasons disallow the changing of SNMP
credentials. To reduce risk from this vulnerability, the following Automation
Studio versions disable the SNMP service by default in newly created AS
projects:
* AS 4.6.5 (Planned release date: 2020-03-27) and higher
* AS 4.7.3 (Planned release date: 2020-04-10) and higher
* AS 4.8.2 (Planned release date: 2020-06-11) and higher
B&R reports the above-mentioned dates denoted as planned are preliminary and
may be subject to change. Registered users may approach their local B&R
service organization in case of questions.
B&R recommends that affected users evaluate their need for the SNMP service
and disable it if possible.
For more information related to this vulnerability please refer to the [B&R
advisory](https://www.br-automation.com/en-us/service/cyber-security/).
For additional information and support, please contact [B&R
service](http://www.br-automation.com/).
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target this vulnerability.