# ICS Advisory (ICSA-16-348-05)
## Siemens S7-300/400 PLC Vulnerabilities (Update E)
Original release date: March 10, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-16-348-05)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-16-348-05)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-16-348-05)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** SIMATIC S7-300 and SIMATIC S7-400
* **Vulnerabilities:** Information Exposure, Improper Input Validation
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the advisory update titled
ICSA-16-348-05 SIEMENS S7-300/400 PLC Vulnerabilities (Update D) that was
published January 25, 2018, to the ICS webpage on us-cert.gov.
## 3\. RISK EVALUATION
Successful exploitation of these vulnerabilities could lead to a denial-of-
service condition or result in credential disclosure.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
The following products are affected:
**\--------- Begin Update E Part 1 of 1 ---------**
* SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) all versions
* SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) all versions
* SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) all versions
* SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) all versions (only affected by CVE-2016-9159)
### 4.2 VULNERABILITY OVERVIEW
#### 4.2.1 [INFORMATION EXPOSURE
CWE-200](https://cwe.mitre.org/data/definitions/200.html)
An attacker with network access to Port 102/TCP (ISO-TSAP) or via Profibus
could obtain credentials from the PLC if Protection-Level 2 is configured on
the affected devices.
[CVE-2016-9159](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2016-9159)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N)).
#### 4.2.2 [IMPROPER INPUT VALIDATION
CWE-20](https://cwe.mitre.org/data/definitions/20.html)
Specially crafted packets sent to Port 80/TCP could cause the affected devices
to go into defect mode. A cold restart is required to recover the system.
[CVE-2016-9158](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2016-9158)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N)).
**\--------- End Update E Part 1 of 1 ---------**
### 4.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Energy, Food and Agriculture, and Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 4.4 RESEARCHER
Zhu WenZhe from Beijing Acorn Network Technology reported these
vulnerabilities to CISA.
## 5\. MITIGATIONS
Siemens provides the following firmware versions to resolve CVE-2016-9158:
* SIMATIC S7-300 CPU family: [Update to v3.X.14](https://support.industry.siemens.com/cs/ww/en/ps/13752/dl)
* SIMATIC S7-400 PN v6: [Update to v6.0.6](https://support.industry.siemens.com/cs/de/en/view/109474874)
* SIMATIC S7-400 v7 CPU family: [Update to v7.0.2](https://support.industry.siemens.com/cs/ww/en/view/109752685)
* SIMATIC S7-410 v8 CPU family: [Update to v8.2](https://support.industry.siemens.com/cs/ww/en/view/109476571)
Siemens also recommends the following mitigations:
* Deactivate the web server.
* Apply Protection-Level 3 read/write protection.
* Apply cell protection concept.
* Apply defense-in-depth strategies.
* Use VPN for protecting network communication between cells.
* For SIMATIC S7-CPU 410 CPUs: Activate Field Interface Security in PCS 7 V9.0 and use a CP 443-1 Adv. to communicate with ES/OS in order to mitigate vulnerability 2 (CVE-2016-9159).
Siemens strongly recommends users protect network access with appropriate
mechanisms (e.g., firewalls, segmentation, VPN). Siemens also advises that
users configure the operational environment according to [Siemens' Operational
Guidelines for Industrial Security](https://www.siemens.com/cert/operational-
guidelines-industrial-security).
For more information on these vulnerabilities and more detailed mitigation
instructions, please see Siemens Security Advisory
[SSA-731239](http://www.siemens.com/cert/advisories).
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.