# ICS Advisory (ICSA-20-084-02)
## Schneider Electric IGSS SCADA Software
Original release date: March 24, 2020 | Last revised: April 03, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-084-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-084-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-084-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.8**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Schneider Electric
* **Equipment:** IGSS (Interactive Graphical SCADA System)
* **Vulnerabilities:** Path Traversal, Missing Authentication for Critical Function
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could result in unauthorized
access to sensitive data and functions.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of IGSS are affected:
* Versions 14 and prior using the service IGSSupdate
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH
TRAVERSAL') CWE-22](https://cwe.mitre.org/data/definitions/22.html)
The affected product could allow a remote unauthenticated attacker to read
arbitrary files on the device.
[CVE-2020-7478](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-7478)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N)).
#### 3.2.2 [MISSING AUTHENTICATION FOR CRITICAL FUNCTION
CWE-306](https://cwe.mitre.org/data/definitions/306.html)
The affected product could allow a local user to execute processes that
otherwise require escalation privileges when sending local network commands to
the IGSS update service.
[CVE-2020-7479](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-7479)
has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been
calculated; the CVSS vector string is
([AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Commercial Facilities, Critical Manufacturing, Energy
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** France
### 3.4 RESEARCHER
sl4v, working with Trend Micro's Zero Day Initiative, reported these
vulnerabilities to CISA.
## 4\. MITIGATIONS
Schneider Electric has provided IGSS14 Version 14.0.0.20009 to address these
vulnerabilities. Users are recommended to update to [IGSS Version
14](http://igss.schneider-electric.com/igss/igssupdates/v140/IGSSUPDATE.zip).
Alternatively, the following workarounds and mitigations can be applied to
reduce risk:
* Disable the IGSS Update service when it is not required installing updates using the service.
* Keep the infrastructure offline and do not allow Windows login and network access for untrusted people and sources.
For more information, see the [Schneider Electric security
notification](https://www.se.com/ww/en/download/document/SEVD-2020-070-01/).
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
* Ensure the least-privilege user principle is followed.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.