# ICS Advisory (ICSA-20-016-01)
## Schneider Electric Modicon Controllers (Update A)
Original release date: March 31, 2020 | Last revised: April 03, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-016-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-016-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-016-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Schneider Electric
* **Equipment:** Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium
* **Vulnerability:** Improper Check for Unusual or Exceptional Conditions
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled
ICSA-20-016-01 Schneider Electric Modicon Controllers that was published
January 16, 2020, on the ICS webpage on us-cert.gov.
## 3\. RISK EVALUATION
Successful exploitation of this vulnerability could result in a denial-of-
service condition.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
The following versions of Modicon controllers, a PLC, are affected:
For
[CVE-2019-6857](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6857),
the following Modicon controllers are affected:
* Modicon M580, all versions prior to v2.80
* Modicon M340, all versions prior to v3.01
* Modicon Premium, all versions prior to v3.20
* Modicon Quantum, all versions prior to v3.60
For
[CVE-2019-6856](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6856)
and
[CVE-2018-7794](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-7794),
the following Modicon controllers are affected:
* Modicon M580, all versions prior to v2.80
* Modicon M340, all versions prior to v3.01
* Modicon Premium, all versions prior to v3.20
* Modicon Quantum, all versions prior to v3.52
### 4.2 VULNERABILITY OVERVIEW
#### 4.2.1 [IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS
CWE-754](https://cwe.mitre.org/data/definitions/754.html)
This vulnerability could cause a denial-of-service condition in the controller
when reading specific memory blocks using Modbus TCP.
[CVE-2019-6857](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6857)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
#### 4.2.2 [IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS
CWE-754](https://cwe.mitre.org/data/definitions/754.html)
This vulnerability could cause a denial-of-service condition when writing
specific physical memory blocks using Modbus TCP.
[CVE-2019-6856](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6856)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
#### 4.2.3 [IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS
CWE-754](https://cwe.mitre.org/data/definitions/754.html)
This vulnerability could cause a denial-of-service condition when reading data
with invalid index using Modbus TCP.
**\--------- Begin Update A Part 1 of 1 ---------**
[CVE-2018-7794](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-7794)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
**\--------- End Update A Part 1 of 1 ---------**
### 4.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Commercial Facilities, Critical Manufacturing, and Energy
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** France
### 4.4 RESEARCHER
Younes Dragoni of Nozomi Networks reported this vulnerability to CISA.
## 5\. MITIGATIONS
Schneider Electric has developed the following mitigations:
Specific Modicon M580 firmware v3.10 is available at:
* [BMEP584040](https://www.schneider-electric.com/en/download/document/M580_BMEP584040_SV3.10/)
* [BMEH584040 and C](https://www.schneider-electric.com/en/download/document/M580_BMEP584040_SV3.10/)
* [BMEP586040 and C](https://www.schneider-electric.com/en/download/document/M580_BMEP586040_SV3.10/)
* [BMEH586040 and C](https://www.schneider-electric.com/en/download/document/M580_BMEH586040_SV3.10/)
* [BMEP581020 and H](https://www.schneider-electric.com/en/download/document/M580_BMEP581020_SV3.10/)
* [BMEP582020 and H](https://www.schneider-electric.com/en/download/document/M580_BMEP582020_SV3.10/)
* [BMEP582040 and H](https://www.schneider-electric.com/en/download/document/M580_BMEP582040_SV3.10/)
* [BMEP583020](https://www.schneider-electric.com/en/download/document/M580_BMEP583020_SV3.10/)
* [BMEP583040](https://www.schneider-electric.com/en/download/document/M580_BMEP583040_SV3.10/)
* [BMEP584020](https://www.schneider-electric.com/en/download/document/M580_BMEP584020_SV3.10/)
* [BMEP585040 and C](https://www.schneider-electric.com/en/download/document/M580_BMEP585040_SV3.10/)
* [BMEH582040 and C](https://www.schneider-electric.com/en/download/document/M580_BMEH582040_SV3.10/)
* [BMEP584040S](https://www.schneider-electric.com/en/download/document/M580_BMEP584040S_SV3.10/)
* [BMEH584040S](https://www.schneider-electric.com/en/download/document/M580_BMEH584040S_SV3.10/)
* [BMEH586040S](https://www.schneider-electric.com/en/download/document/M580_BMEH586040S_SV3.10/)
* [BMEP582040S](https://www.schneider-electric.com/en/download/document/M580_BMEP582040S_SV3.10/)
Modicon M340 firmware v3.20 is available at:
* [BMXP3420302 and CL and H](https://www.schneider-electric.com/en/download/document/BMXP3420302_Firmwares/)
* [BMXP342020 and H](https://www.schneider-electric.com/en/download/document/BMXP342020_Firmwares/)
* [BMXP342000](https://www.schneider-electric.com/en/download/document/BMXP342000_Firmwares/)
* [BMXP341000 and H](https://www.schneider-electric.com/en/download/document/BMXP341000_Firmwares/)
* [BMXP3420102 and CL](https://www.schneider-electric.com/en/download/document/BMXP3420102_Firmwares/)
* [BMXP3420302](https://www.schneider-electric.com/en/download/document/BMXP3420302_Firmwares/)
Modicon Premium v3.20 firmware is available by contacting Schneider Electric
customer support.
Modicon Quantum firmware v3.60 is available at:
* [140CPU65150 [C] and 140CPU65160 [C]](https://www.schneider-electric.com/en/download/document/Quantum_140CPU651X0_SV3.60)
* [140CPU65260 [C]](https://www.schneider-electric.com/en/download/document/Quantum_140CPU65260_SV3.60)
* [140CPU67261 [C]](https://www.schneider-electric.com/en/download/document/Quantum_140CPU67261_SV3.60)
* [140CPU67060 [C]](https://www.schneider-electric.com/en/download/document/Quantum_140CPU67060_SV3.60)
* [140CPU67160 [C]](https://www.schneider-electric.com/en/download/document/Quantum_140CPU67160_SV3.60)
* [140CPU67260 [C]](https://www.schneider-electric.com/en/download/document/Quantum_140CPU67260_SV3.60)
* [140CPU65860 [C]](https://www.schneider-electric.com/en/download/document/Quantum_140CPU65860_SV3.60)
* [140CPU67861 [C]](https://www.schneider-electric.com/en/download/document/Quantum_140CPU67861_SV3.60)
* 140CPU65160S
* Please contact Schneider Electric customer support to get the Quantum v3.60 firmware
* 140CPU67160S
* Please contact Schneider Electric customer support to get the Quantum v3.60 firmware
Schneider Electric strongly recommends following industry cybersecurity best
practices such as:
* Locate control and safety system networks and remote devices behind firewalls, and isolate them from the business network.
* Physical controls should be in place so that no unauthorized person would have access to the ICS and safety controllers, peripheral equipment, or the ICS and safety networks.
* All controllers should reside in locked cabinets and never be left in the "Program" mode.
* All programming software should be kept in locked cabinets and should never be connected to any network other than the network for which the devices are intended.
* All methods of mobile data exchange with the isolated network, such as CDs, USB drives, etc., should be scanned before use in the terminals or any node connected to these networks.
* Laptops that have connected to any other network besides the intended network should never be allowed to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
For more information on this vulnerability and the associated upgrade, please
see [Schneider Electric's SEVD-2019-344-01](https://www.schneider-
electric.com/en/download/document/SEVD-2019-344-01/)
For more details and assistance on how to protect during installation, please
contact a [Schneider Electric representative](http://www2.schneider-
electric.com/sites/corporate/en/support/cybersecurity/cybersecurity.page)
and/or [Schneider Electric Industrial Cybersecurity
Services](https://www.schneider-electric.com/en/work/services/field-
services/industrial-automation/industrial-cybersecurity/industrial-
cybersecurity.jsp). These organizations are aware of this situation and can
support you through the process.
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target this vulnerability.
暂无评论