# ICS Advisory (ICSA-20-133-01)
## Eaton Intelligent Power Manager
Original release date: May 12, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-133-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-133-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-133-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 8.8**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Eaton
* **Equipment:** Intelligent Power Manager
* **Vulnerabilities:** Improper Input Validation, Incorrect Privilege Assignment
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to
perform command injection or code execution and allow non-administrator users
to manipulate the system configurations.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of Intelligent Power Manager, a software monitoring and
management platform, are affected:
* Intelligent Power Manager v1.67 and prior
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [IMPROPER INPUT VALIDATION
CWE-20](https://cwe.mitre.org/data/definitions/20.html)
The affected product may not validate import configuration file names
properly, which could allow an attacker to perform command injection or code
execution.
[CVE-2020-6651](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-6651)
has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H)).
#### 3.2.2 [INCORRECT PRIVILEGE ASSIGNMENT
CWE-266](https://cwe.mitre.org/data/definitions/266.html)
The affected product may allow non-administrator users to upload the system
configuration files by sending specially crafted requests, which could allow
non-administrator users to manipulate the system configurations.
[CVE-2020-6652](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-6652)
has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been
calculated; the CVSS vector string is
([AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Energy
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Ireland
### 3.4 RESEARCHER
Sivathmican Sivakumaran of Trend Micro's Zero Day Initiative reported these
vulnerabilities to CISA.
## 4\. MITIGATIONS
Eaton has released [Intelligent Power Manager
v1.68](https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-
distribution/eaton-intelligent-power-manager/download-eaton-intelligent-power-
manager-ipm.html) to address the reported vulnerabilities.
To prevent the exploitation of the issues and safeguard the software from
malicious entities, Eaton recommends blocking Ports 4679 and 4680 at the
enterprise network or home network where Intelligent Power Manager software is
installed and used.
For additional information please see the [Eaton Vulnerability
Advisory](https://www.eaton.com/content/dam/eaton/company/news-
insights/cybersecurity/security-bulletins/eaton-vulnerability-advisory-
intelligent-power-manager-v1-1.pdf).
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.