# ICS Advisory (ICSA-20-177-02)
## Rockwell FactoryTalk Services Platform XXE
Original release date: June 25, 2020 | Last revised: June 30, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-177-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-177-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-177-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 8.4**
* **ATTENTION:** Low skill level to exploit
* **Vendor:** Rockwell Automation
* **Equipment:** FactoryTalk Services Platform
* **Vulnerability:** Improper Restriction of XML External Entity Reference
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could lead to a denial-of-
service condition and to the arbitrary reading of any local file via system
level services.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of FactoryTalk Services Platform are affected:
* Versions 6.11.00 and earlier
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE
CWE-611](https://cwe.mitre.org/data/definitions/611.html)
A local, authenticated attacker could use an XML External Entity (XXE) attack
to exploit weakly configured XML files to access local or remote content. A
successful exploit could potentially cause a denial-of-service condition and
allow the attacker to arbitrarily read any local file via system-level
services.
[CVE-2020-14478](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-14478)
has been assigned to this vulnerability. A CVSS v3 base score of 8.4 has been
assigned; the CVSS vector string is
([AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Food and Agriculture, Transportation Systems, Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** United States
### 3.4 RESEARCHER
Applied Risk reported this vulnerability to Rockwell.
## 4\. MITIGATIONS
Affected users are encouraged to use Rockwell Automation Knowledgebase article
[25612](https://rockwellautomation.custhelp.com/app/answers/detail/a_id/25612)
to determine if FactoryTalk Services Platform is installed.
For more information please see Rockwell Automation Knowledgebase article
[1092746](https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1092746)
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target this vulnerability. This
vulnerability is not exploitable remotely.
暂无评论