# ICS Advisory (ICSA-17-243-01)
## Siemens OPC UA Protocol Stack Discovery Service (Update D)
Original release date: August 11, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-17-243-01-0)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-17-243-01-0)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-17-243-01-0)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 8.2**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** SIMATIC
* **Vulnerabilities:** Improper restriction of XML external entity reference
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled
ICSA-17-243-01 Siemens OPC UA Protocol Stack Discovery Service (Update C) that
was published February 5, 2019, on the ICS webpage on us-cert.gov.
## 3\. RISK EVALUATION
Successful exploitation of this vulnerability may allow an attacker to access
various resources.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
Siemens reports that the vulnerability affects the following industrial
products, which use the Discovery Service of the OPC UA protocol stack by the
OPC foundation:
* SIMATIC IT Production Suite: Versions between v6.5 and v7.1
**\--------- Begin Update D Part 1 of 2 ---------**
* SIMATIC NET PC Software: v14 and prior and versions prior to v15
**\--------- End Update D Part 1 of 2 ---------**
### 4.2 VULNERABILITY OVERVIEW
### 4.2.1 [IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE ('XXE')
CWE-611](https://cwe.mitre.org/data/definitions/611.html)
By sending specially crafted packets to the OPC Discovery Server at Port
4840/TCP, an attacker may be able to cause the system to access various
resources chosen by the attacker.
[CVE-2017-12069](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-12069)
has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been
calculated; the CVSS vector string is
[(AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H)](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H).
### 4.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Energy, Food and Agriculture, Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 4.4 RESEARCHER
Sergey Temnikov of Kaspersky Lab reported this vulnerability to Siemens.
## 5\. MITIGATIONS
Siemens provides fixes for the following products and recommends users upgrade
to the newest version:
* SIMATIC IT Production Suite:
Contact local support to update to v7.1
**\--------- Begin Update D Part 2 of 2 ---------**
* SIMATIC NET PC Software: [Update to Version 15 or later](https://support.industry.siemens.com/cs/ww/en/view/109762690)
**\--------- End Update D Part 2 of 2 ---------**
* SIMATIC WinCC Runtime Professional: [Update to v14 SP1](https://support.industry.siemens.com/cs/ww/en/view/109746276)
Siemens has identified the following specific workarounds and mitigations that
customers can apply to reduce the risk:
* Operating the devices only within trusted networks.
* [Turn off the discovery service after commissioning or block it on the local firewall](https://support.industry.siemens.com/cs/ww/en/view/109749461),
* Apply cell protection concept,
* Use VPN for protecting network communication between cells, and
* Apply defense in depth.
Siemens recommends users protect network access with appropriate mechanisms
such as firewalls, segmentation, and VPNs. Siemens also advises that users
configure the operational environment according to [Siemens Operational
Guidelines for Industrial Security](https://www.siemens.com/cert/operational-
guidelines-industrial-security).
For more information on this vulnerability and more detailed mitigation
instructions, please see [Siemens Security Advisory
SSA-535640](http://www.siemens.com/cert/advisories).
The [OPC Foundation also published a security bulletin](https://opcfoundation-
onlineapplications.org/faq/SecurityBulletins/OPC_Foundation_Security_Bulletin_CVE-2017-12069.pdf)
for this vulnerability.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target this vulnerability.