# ICS Advisory (ICSA-20-042-04)
## Siemens PROFINET-IO Stack (Update B)
Original release date: August 11, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-042-04)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-042-04)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-042-04)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** Siemens PROFINET-IO Stack
* **Vulnerability:** Uncontrolled Resource Consumption
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the advisory update titled
ICSA-20-042-04 Siemens PROFINET-IO Stack (Update A) that was published March
10, 2020, on the ICS webpage on us-cert.gov.
## 3\. RISK EVALUATION
Successful exploitation of this vulnerability could lead to a denial-of-
service condition.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
Products that include the Siemens PROFINET-IO (PNIO) stack in versions prior
to v06.00 are affected. Additionally, Siemens recommends other vendors of
PROFINET devices check their products for vulnerable versions of the Siemens
PNIO stack as part of the Siemens Development/Evaluation Kits.
* Development/Evaluation Kits for PROFINET IO:
* DK Standard Ethernet Controller: all versions
* EK-ERTEC 200: all versions prior to 4.5
* EK-ERTEC 200P: all versions prior to 4.6
* PROFINET Driver for Controller: all version prior to 2.1
* RUGGEDCOM RM1224: all versions prior to 4.3
* SCALANCE M-800 / S615: all versions prior to 4.3
* SCALANCE W700 IEEE 802.11n: all versions prior to 6.0.1
* SCALANCE X-200 switch family (incl. SIPLUS NET variants): all versions
* SCALANCE X-200IRT switch family (incl. SIPLUS NET variants): all versions prior to 5.3
* SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants): all versions
* SCALANCE XB-200, XC-200, XP-200, XF-200BA and XR-300WG: all versions prior to 3.0
* SCALANCE XM-400 switch family: all versions prior to 6.0
* SCALANCE XR-500 switch family: all versions prior to 6.0
* SIMATIC CP 1616 and CP 1604: all versions prior to 2.8
* SIMATIC CP 343-1 (incl. SIPLUS NET variants): all versions
* SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variants): all versions
* SIMATIC CP 343-1 ERPC: all versions
* SIMATIC CP 343-1 LEAN (incl. SIPLUS NET variants): all versions
* SIMATIC CP 443-1 (incl. SIPLUS NET variants): all versions
* SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variants): all versions
* SIMATIC CP 443-1 OPC UA: all versions
* SIMATIC ET200AL IM 157-1 PN: all versions
* SIMATIC ET200M IM153-4 PN IO HF (incl. SIPLUS variants): all versions
* SIMATIC ET200M IM153-4 PN IO ST (incl. SIPLUS variants): all versions
* SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants): all versions prior to 4.2.0
* SIMATIC ET200MP IM155-5 PN ST (incl. SIPLUS variants): all versions prior to 4.1.0
**\--------- Begin Update B Part 1 of 1 ---------** -
* SIMATIC ET200ecoPN (except 6ES7141-6BG00- 0BB0, 6ES7141-6BH00-0BB0, 6ES7142-6BG00- 0BB0, 6ES7142-6BR00-0BB0, 6ES7143-6BH00- 0BB0, 6ES7146-6FF00-0AB0 and 6ES7148- 6JD00-0AB0): All versions
**\--------- End Update B Part 1 of 1 ---------**
* SIMATIC ET200S (incl. SIPLUS variants): all versions
* SIMATIC ET200SP IM155-6 PN Basic (incl. SIPLUS variants): all versions
* SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants): all versions prior to 3.3.1
* SIMATIC ET200SP IM155-6 PN ST (incl. SIPLUS variants): all versions prior to 4.1.0
* SIMATIC ET200ecoPN (except 6ES7148-6JD00-0AB0 and 6ES7146-6FF00-0AB0): all versions
* SIMATIC ET200pro, IM 154-3 PN HF: all versions
* SIMATIC ET200pro, IM 154-4 PN HF: all versions
* SIMATIC IPC Support, Package for VxWorks: all versions
* SIMATIC MV400 family: all versions
* SIMATIC PN/PN Coupler 6ES7158-3AD01-0XA0 (incl. SIPLUS NET variant): all versions
* SIMATIC RF180C: all versions
* SIMATIC RF182C: all versions
* SIMATIC RF600 family: all versions prior to 3
* SINAMICS DCP: all versions prior to 1.3
* SOFTNET-IE PNIO: all versions
### 4.2 VULNERABILITY OVERVIEW
#### 4.2.1 [UNCONTROLLED RESOURCE CONSUMPTION
CWE-400](https://cwe.mitre.org/data/definitions/400.html)
Profinet-IO (PNIO) stack versions prior v06.00 do not properly limit internal
resource allocation when multiple legitimate diagnostic package requests are
sent to the DCE-RPC interface. This could lead to a denial-of-service
condition due to lack of memory for devices that include a vulnerable version
of the stack.
[CVE-2019-13946](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-13946)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
### 4.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Critical Manufacturing
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 4.4 RESEARCHER
Yuval Ardon and Matan Dobrushin of OTORIO reported this vulnerability to CISA
and Siemens.
## 5\. MITIGATIONS
Siemens has released updates for several affected products and recommends
users update to the new version. Siemens is preparing further updates and
recommends specific countermeasures until patches are available.
* Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200: [Update to v4.5 Patch 01 ](https://support.industry.siemens.com/cs/ww/en/view/109760397/)
* Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P: [Update to v4.6](https://support.industry.siemens.com/cs/ww/en/view/109765183/)
* PROFINET Driver for Controller: [Update to v2.1 Patch 03](https://support.industry.siemens.com/cs/ww/en/view/109768047/)
* SCALANCE M-800 / S615: [Update to v6.1.2](https://support.industry.siemens.com/cs/ww/en/view/109772130/)
* SCALANCE W700 IEEE 802.11n: [Update to v6.4](https://support.industry.siemens.com/cs/ww/en/view/109773308)
* SCALANCE X-200IRT switch family: [Update to v5.4.2](https://support.industry.siemens.com/cs/ww/en/view/109763309/)
* SCALANCE XB-200, XC-200, XP-200, XF-200BA and XR-300WG: [Update to v4.1](https://support.industry.siemens.com/cs/ww/en/view/109762982/)
* SCALANCE XM-400 switch family: [Update to v6.2.3](https://support.industry.siemens.com/cs/ww/en/view/109771191/)
* SCALANCE XR-500 switch family: [Update to v6.2.3](https://support.industry.siemens.com/cs/ww/en/view/109771191/)
* SIMATIC CP 1616 and CP 1604: [Update to v2.8.1](https://support.industry.siemens.com/cs/ww/en/view/109768663/)
* SIMATIC ET200MP IM155-5 PN HF: [Update to v4.2.0](https://support.industry.siemens.com/cs/ww/en/view/93012181)
* SIMATIC ET200MP IM155-5 PN ST: [Update to v4.1.0](https://support.industry.siemens.com/cs/ww/en/view/78647504/)
* SIMATIC ET200SP IM155-6 PN HF: [Update to v4.2.2](https://support.industry.siemens.com/cs/ww/en/view/85624387/)
* SIMATIC ET200SP IM155-6 PN ST: [pdate to v4.1.0](https://support.industry.siemens.com/cs/ww/en/view/78647504/)
* SIMATIC RF600 family: [Update to v3.2.1](https://support.industry.siemens.com/cs/ww/en/view/109768501)
* SINAMICS DCP: [Update to v1.3](https://support.industry.siemens.com/cs/ww/en/view/109773826/)
Siemens has identified the following specific workarounds and mitigations
users can apply to reduce the risk:
* If possible, disable PROFINET
* SCALANCE M-800 / S615 and RUGGEDCOM RM1224: Create a firewall rule that blocks the PROFINET Context Manager port (34964/UDP).
As a general security measure, Siemens strongly recommends users protect
network access to devices with appropriate mechanisms. In order to operate the
devices in a protected IT environment, Siemens recommends users configure the
environment according to [Siemens' operational guidelines for Industrial
Security](https://cert-portal.siemens.com/operational-guidelines-industrial-
security.pdf), and follow the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For more information on the vulnerability and more detailed mitigation
instructions, please see Siemens security advisory
[SSA-780073](http://www.siemens.com/cert/advisories)
For more information on this vulnerability see also [ICS Advisory
ICSA-19-353-01 Moxa EDS Ethernet Switches](https://www.us-
cert.gov/ics/advisories/icsa-19-353-01).
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target this vulnerability.
暂无评论