# ICS Advisory (ICSA-20-224-08)
## Siemens SICAM A8000 RTUs
Original release date: August 11, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-224-08)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-224-08)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-224-08)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 8.3**
* **ATTENTION:** Exploitable remotely
* **Vendor:** Siemens
* **Equipment:** SICAM A8000
* **Vulnerability:** Cross-site Scripting
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could compromise the
confidentiality, integrity, and availability of the web application.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of SICAM A8000 RTUs are affected:
* SICAM WEB firmware: all versions prior to C05.30
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION
('CROSS-SITE SCRIPTING')
CWE-79](https://cwe.mitre.org/data/definitions/79.html)
The login screen does not sufficiently sanitize input, which enables an
attacker to generate specially crafted log messages. If an unsuspecting user
views the log messages via a web browser, these log messages might be
interpreted and executed as code by the web application. This cross-site
scripting (XSS) vulnerability might compromise the confidentiality, integrity,
and availability of the web application.
[CVE-2020-15781](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-15781)
has been assigned to this vulnerability. A CVSS v3 base score of 8.3 has been
calculated; the CVSS vector string is
([AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Energy
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 3.4 RESEARCHER
Emma Good from KTH Royal Institute of Technology reported this vulnerability
to Siemens.
## 4\. MITIGATIONS
Siemens recommends users update to the [latest version,
v05.30](https://support.industry.siemens.com/cs/us/en/view/109780765).
Applying the update causes the device/module to go through a single restart
cycle. Siemens also recommends users:
* Restrict access to Port 443/TCP
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to the [Siemens operational guidelines for Industrial
Security](https://cert-portal.siemens.com/operational-guidelines-industrial-
security.pdf) and following the recommendations in the product manuals.
For additional information, please refer to Siemens Security Advisory
[SSA-370042](https://cert-portal.siemens.com/productcert/pdf/ssa-370042.pdf)
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target this vulnerability. High skill
level is needed to exploit.